Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Shouldice Arena

From FireAlarmPedia
Revision as of 21:13, 12 October 2024 by Alberta Fire Alarms (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Mircom FX-2000
FACP Location: Main Lobby
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: 2010s
Year Opened: 1972

Shouldice Arena is an ice hockey arena located at 4900 13 Ave NW, Calgary, AB. It is owned and operated by the City of Calgary. The building was built in 1972, and was remodeled in the late 1990s. The fire alarm system was upgraded around 1999, and again in 2007.

System Specifications (2007-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main lobby. The system runs Mircom’s CLIP addressable protocol, and the system coding is continuous.
This system replaced an EST 6632 in 2007 as part of that year’s upgrade project.

Notification Appliances[edit | edit source]

All audible notification appliances except for one are Edwards 439D-10AWC vibrating bells (10” gong).
There are EST “Integrity” 202-5A-T remote strobes (red, wall-mount, 15cd) in each dressing room and next to all Edwards bells .
The universal dressing room has a Mircom BL-6B motor bell (6” gong) on a Wheelock RSSP-24MCW strobe plate (red, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Mircom MS-401AD addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Mircom MIX-5251RA addressable 135 degree fixed temperature/rate-of-rise heat detectors throughout the arena.
The flood room has a Mircom MIX-5251HBA addressable 135-degree fixed temperature heat detector.
All detectors are mounted on System Sensor B710LPA bases.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistor plates on all signal circuits.