Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Spruce Ridge Gardens

From FireAlarmPedia
Revision as of 15:03, 13 October 2024 by Alberta Fire Alarms (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Mircom FX-2000
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: N/A
Year Opened: 2013

Spruce Ridge Gardens is an apartment building located at 19A Hemlock Crescent SW, in Calgary, Alberta, Canada. The building is owned and managed by Boardwalk. The building was built in 2013, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Mircom’s CLIP addressable protocol, and the system coding is temporal.

Booster Panels[edit | edit source]

There is a Mircom INX-10 addressable booster power supply in the main floor electrical room.

Notification Appliances[edit | edit source]

All common areas have Mircom “Select-A-Horn/Strobe” FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).
All suite bedrooms have Mircom MH-S25WA silenceable mini-horns (white, wall-mount).
Some suites have System Sensor MHWZA silenceable mini-horns (white, wall-mount) as deficiency replacements.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Mircom MS-401AD addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Mircom MIX-2251BA addressable photoelectric smoke detectors in all common areas.
These are mounted on System Sensor B210LPA bases in most areas, and on System Sensor B200SRA sounder bases in the parkade elevator lobby and the centre and west stairwells.
There are System Sensor DNRA addressable duct detectors with Mircom MIX-2251BA addressable photoelectric heads on all make-up air units.

Modules[edit | edit source]

There are Mircom MIX-M500DMA addressable dual-input monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Mircom MIX-M500RA addressable relay modules for elevator homing and MUA shutdown.
There are System Sensor M500XA isolator modules on the SLC.
There are Mircom CSIS-202A suite signaling isolators between each unit.

EOLs[edit | edit source]

There are Mircom MP-300 end of line resistor plates on all common-area signaling circuits and sprinkler circuits.