NAIT Building Y - Spartan Centre for Instrumentation Technology & Petro-Canada Centre for Millwright Technology
More actions
System Specifications |
---|
FACP: Simplex 4100U FACP Location: Unknown System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 70VRMS (audible) 24VDC (visual) System Coding: 20BPM (alert) Slow Whoop + Custom Message (Alarm) Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 2007 |
The Northern Alberta Institute of Technology is a technical college/trades school located in Edmonton, Alberta, Canada. This page will cover Building Y, which houses the Spartan Centre for Instrumentation Technology and the Petro-Canada Centre for Millwright Technology. It was built in 2007, and the fire alarm system is original.
System Specifications (2007-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Simplex 4100U addressable fire alarm system. The panel location is unknown. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice-evacuation. The system is configured for two-stage operation. The alert signal is 20BPM, followed by slow whoop and a custom message for the alarm signal.
Annunciators[edit | edit source]
There is a Simplex 4100-9212 “remote command center” LCD annunciator in a 3 bay cabinet in the main entrance vestibule
Notification Appliances[edit | edit source]
All notification appliances are new old stock.
Most notification appliances are Wheelock E-9070-LS-24-CFW speaker/strobes (white, ceiling-mount, 15cd), these are also installed in bathrooms.
The upper floors of Spartan have Wheelock ET-1070-LSM-24-VFW speaker/strobes (white, wall-mount, 15/75cd).
There are Wheelock ET-1070-LSM-24-VFR speaker/strobes (red, wall-mount, 15/75cd) in the stairwells and the door to Petro-Canada Centre.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Simplex 4099-9004CA addressable two-stage pull stations.
Automatic Detection Devices[edit | edit source]
There are Simplex 4098-9714 addressable photoelectric smoke detectors in some areas, mostly elevator lobbies, mounted on 4098-9792 bases.
Modules[edit | edit source]
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules for door release and elevator recall.
EOLs[edit | edit source]
There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.
Voice Evac Message Script[edit | edit source]
Alarm Signal[edit | edit source]
"May I have your attention please! May I have your attention please! There has been a fire alarm condition reported in the building. While this being verified, please leave the building by the nearest exit or exit stairway. Do not use the elevators."