System Specifications
FACP: EST QuickStart QS4 (unconfirmed)
FACP Location: Unknown
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, EST
Date of last known Upgrade: N/A
Year Opened: 2006

Super 8 is a budget hotel chain owned by Wyndham. They are headquartered in Parsippany, New Jersey, USA, and have locations worldwide. This particular hotel is located at 5220 2 Avenue, in Edson, Alberta, Canada. The hotel opened in 2006, and the fire alarm system is original.

System Specifications (2006-present)[edit | edit source]

Please note that some system information is unknown. This page should not be used for official purposes. Fire Alarmpedia is not responsible for any issues caused by inaccuracies.

FACP[edit | edit source]

The building is protected by an EST addressable fire alarm system. The model of the panel is unknown, but is believed to be a QuickStart QS4. The system runs EST’s Signature addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All notification appliances are from EST's "Genesis" line of products.

Common Areas[edit | edit source]

All common area notification appliances are EST G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd).

Guest Rooms[edit | edit source]

The guest rooms have EST G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 110cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the hotel, mounted on SIGA-SB bases. There is also a sprinkler system with waterflow detection.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.