The Home Depot (Whitemud)

From FireAlarmPedia
Revision as of 12:03, 14 October 2024 by Alberta Fire Alarms (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier AFP-200C
FACP Location: Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: N/A
Year Opened: 2006

The Home Depot is an American home improvement store chain. This particular location is located at 4430 17 St NW, Edmonton, AB. The store opened in 2006, and the fire alarm system is original.

System Specifications (2006-present)[edit | edit source]

FACP[edit | edit source]

The store is protected by a Notifier AFP-200C addressable fire alarm system. The panel is located in an electrical room. The system runs Notifier's CLIP addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is a Notifier LCD-80TM LCD annunciator located in the main entrance vestibule.

Notification Appliances[edit | edit source]

All notification appliances are System Sensor "SpectrAlert" P1224MCA horn/strobes (red, wall-mount, set to electromechanical/15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

None noticed, waterflow protection.

Modules[edit | edit source]

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.

List of known activations[edit | edit source]

November 11, 2022: tripped into alarm. Edmonton Fire Rescue Services on scene, alarms still going off for 30 minutes. Customers complained about the volume of the alarm. System eventually reset, fire department confirmed false alarm.