University Station

From FireAlarmPedia
Revision as of 17:57, 14 October 2024 by Alberta Fire Alarms (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Simplex 4007ES

FACP Location: Unknown
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC

System Coding: Temporal

Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: 2019
Year Opened: 1987


University Station is a Red Line CTrain LRT station in Calgary. The station primarily serves the University of Calgary, the largest university in Southern Alberta. The station is located at-grade, in the median of Crowchild Trail. This station has a small interior building and an overpass. The station opened on September 7th, 1987, and was renovated in 2019. The station received a new fire alarm system as part of the renovations.

System Specifications[edit | edit source]

FACP[edit | edit source]

The station is protected by a Simplex 4007ES addressable fire alarm system. The panel location is unknown, but the model is speculated based on the size of the building, age of the system, and the initiating devices on the system. The system runs Simplex’s IDNet addressable protocol, the system coding is temporal.

Notification Appliances[edit | edit source]

All notification appliances are from Simplex’s “TrueAlert” line of products.

Most of the station has Simplex 4906-9127 horn/strobes (red, wall-mount, 15cd).

The second floor of the building has a Simplex 4901-9820 remote horn (red, wall-mount) on the west side, and a Simplex 4906-9101 remote strobe (red, wall-mount, 15cd) on the east side.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9004 addressable LED single-action pull stations, mounted on Simplex 2975-9178 backboxes.

Automatic Detection Devices[edit | edit source]

There are Simplex “TrueAlarm” detectors throughout the building. Some are Simplex 4098-9714 addressable photoelectric smoke detectors, and some are Simplex 4098-9734 addressable fixed/rate-of-rise heat detectors. All are mounted on Simplex 4098-9792 addressable bases.

EOLs[edit | edit source]

There are Simplex 2081-9040C end-of-line resistor plates on all signal circuits.