Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

North Hill Centre

From FireAlarmPedia
Revision as of 17:40, 14 October 2024 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS2-640C
FACP Location: Food Court Entrance
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Date of last known Upgrade: 2018-19
Year Opened: 1958, 1973, 2000

North Hill Centre was the first shopping mall in Calgary, Alberta. It is located off at 1632 14 Ave NW, Calgary. The mall spans two floors, with professional offices (dental, pediatric and doctor clinics) on the second level. The mall was built in 1958, expanded in 1973, and then majorly renovated in 2000. The fire alarm system is from the 2000 renovation.

System Specifications (2000-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located at the food court entrance. The system runs Notifier's CLIP addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, followed by temporal in alarm signal.

Notification Appliances[edit | edit source]

The notification appliances are mainly System Sensor "SpectrAlert" P2415A horn/strobes (red, wall-mount, 15cd) horn/strobes.

Dollarama opened 2019, and has System Sensor "L-Series" PC2RLA horn/strobes (red, ceiling-mount, bilingual marking, set to 30cd).

Winners opened 2018, and has System Sensor "SpectrAlert Advance" PC2WA (white, ceiling-mount, set to 15cd) horn/strobes.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NFM-950KB conventional single-action two-stage pull stations. These are attached to Notifier MMX-101A addressable modules.

Automatic Detection Devices[edit | edit source]

There are System Sensor CPX-551 addressable ionization smoke detectors throughout the mall, mounted on System Sensor BX501A bases.

There is a Notifier FSP-851A addressable photoelectric smoke detector on the second floor, mounted on a System Sensor B210LPA base as a deficiency replacement.

Modules[edit | edit source]

There are Notifier MMX-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are Notifier CMX-2A addressable relay modules serving various purposes.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.