FACP: Mircom FlexNet FACP Location: Various System Type: Two-Stage Networked Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VFWR (Visual) System Coding: 20BPM (Alert) Temporal (Alarm) Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Year Opened: 2022 |
Oliver East is a luxury apartment building located at 524 10 Ave SW, in Calgary, Alberta, Canada. The building was built in 2022, and the fire alarm system is original.
This page also covers Luca Restaurant.
System Specifications
FACP
The building is protected by a Mircom FlexNet addressable fire alarm system. This is a networked system with 4 nodes; Node 1 is located in the CACF Room on the Main Floor, Node 2 is located in the 7th Floor Electrical Room, Node 3 is located in the 17th Floor Electrical Room, and Node 4 is located in the 26th Floor Electrical Room. The system runs Mircom’s Advanced addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation; the alert signal is a 20BPM tone, and the alarm signal is a temporal tone. Please see below for message scripts and sequence of operation.
Notification Appliances
The upper floor common areas and suite living areas have System Sensor “L-Series” SPSCWLA speaker/strobes (white, ceiling-mount, set to 70V/15cd).
Other areas have System Sensor SPSWLA speaker/strobes (white, wall-mount, set to 70V/15cd).
The suite bedrooms have System Sensor SPCWLA remote speakers (white, ceiling-mount, set to 70V).
The lounge has System Sensor SPSBLA and SLSCBLA speaker/strobes (black, wall/ceiling-mount, assumed model no.).
For outdoor notification, there is a System Sensor “SpectrAlert Advance” SRKA weatherproof remote strobe (red, wall-mount) outside the main entrance.
Initiating Devices
Pull Stations
All pull stations are Mircom MS-402AP addressable two-stage single-action pull stations.
Automatic Detection Devices
There are Mircom MIX-2251APA addressable photoelectric smoke detectors throughout all upper floor common areas, and at the top of each stairwell and elevator shaft.
There is a Mircom MIX-2351APA addressable photoelectric smoke detector in one elevator lobby as a deficiency replacement.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There are System Sensor DNRA duct smoke detector housings with Mircom MIX-2251BA addressable photoelectric heads on all make up air units.
Modules
There are Mircom MIX-M500MAPA addressable monitor modules supervising the kitchen suppression systems, the generator run/trouble contacts, and the sprinkler system’s tamper and flow switches.
There are Mircom MIX-M500RAPA addressable relay modules serving various purposes.
There are Mircom MIX-M500FPA addressable firefighter’s telephone modules supervising all fire phones.
There are System Sensor M500XA isolator modules on all SLCs.
Firefighter’s Telephones
There are Mircom FT-300A firefighter’s telephones at each stairwell exit on every floor.
EOLs
There are Mircom MP-300 end of line resistor plates on all circuits supervised by monitor modules, and all signal circuits.