System Specifications |
---|
FACP: Notifier NFS2-3030C FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2014 Year Opened: 2006 |
River Cree Twin Rinks is the arena located in the River Cree Resort & Casino, located at 300 East Lapotac Blvd, Enoch, Alberta. It houses two NHL-sized rinks. It opened in 2006, and the fire alarm system is mostly original.
System Specifications (2006-present)
FACP
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances
Most notification appliances are System Sensor “SpectrAlert” P2415A horn/strobes (red, wall-mount, 15cd).
There are some System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd) as deficiency replacements.
Initiating Devices
Pull Stations
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors in some areas, mounted on Notifier B710LPA bases.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on each SLC.
EOLs
There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.