System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2012

The Airdrie Fire Department is the fire department serving The City of Airdrie. This page will cover the headquarters building/Chinook Winds Station, located at 2525 Chinook Winds Drive SW, in Airdrie, Alberta, Canada. The building was built in 2012, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is a Notifier LCD2-80 annunciator paired with a Notifier ACM-24AT annunciator in the west entrance vestibule.

Booster Panels[edit | edit source]

There is a Notifier FCPS-24S8C booster power supply next to the main FACP.

Notification Appliances[edit | edit source]

All notification appliances are System Sensor “SpectrAlert Advance” P4RA horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-851A addressable photoelectric smoke detectors throughout most areas.
The elevator shaft has a Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detector.
All aforementioned detectors are mounted on Notifier B710LPA bases.
There is a System Sensor DNRA duct smoke detector with a Notifier FSP-851A addressable photoelectric head on the main HVAC unit.

Modules[edit | edit source]

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.