System Specifications |
---|
FACP: Mircom FX-2000 FACP Location: Mechanical Room System Type: Single-Stage Hybrid-Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: 2020s Year Opened: 1982 |
St. Stephen Protomartyr Ukrainian Catholic Church is a church located at 4903 45 St SW, Calgary, AB. It was originally built in 1982, and was expanded in 1996. The fire alarm system was upgraded in 1997, and partially upgraded around 2012.
System Specifications (2012-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Mircom FX-2000 hybrid-addressable fire alarm system. The panel is located in the mechanical room. The system runs Mircom’s CLIP addressable protocol, and the system coding is continuous.
Notification Appliances[edit | edit source]
Most notification appliances are Edwards 892-2B horn/strobes (red, wall-mount, 1.5cd, electronic).
There are Edwards “Genesis” G1AVRF horn/strobes (red, wall-mount, FIRE marking, set to 15cd) as deficiency replacements.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations except one are Edwards 270-SPO conventional single-action pull stations; there is a mix of original and 1996 ones.
There is a Simplex MS-301C conventional pull station as a deficiency replacement.
Automatic Detection Devices[edit | edit source]
There are a mix of Edwards 245A conventional 135°F fixed-temperature heat detectors and Mirtone 73330 conventional 135°F fixed-temperature heat detectors throughout.
The stairwells have System Sensor “i3” C2W-BA conventional photoelectric smoke detectors.
The chapel has Mircom MIX-2251BA addressable photoelectric smoke detectors, mounted on System Sensor B210LPA bases.
The air handling units have Simplex “TrueAlarm” 4098-9685 2-wire conventional photoelectric duct smoke detectors.
EOLs[edit | edit source]
There are Edwards EOL-P1 end-of-line resistor plates on all conventional and signal circuits.