2930 32 Ave NE, Calgary

From FireAlarmPedia
Revision as of 17:41, 12 January 2025 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS-320C <br />FACP Location: Visions Main Entrance Vestibule <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: 2022 <br />Year Opened: 1981 |} '''2930 32 Ave NE''' is the address of a small shopping plaza in Calga...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS-320C
FACP Location: Visions Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2022
Year Opened: 1981

2930 32 Ave NE is the address of a small shopping plaza in Calgary, Alberta, Canada. The plaza consists of Sofaland and Visions Electronics. The building was built in 1981, and the fire alarm system has been replaced twice: once in 2013, and once in 2022.

System Specifications (2022-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the Visions main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All indoor notification appliances are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor “SpectrAlert Advance” SRKA weatherproof remote strobe (red, wall-mount) outside the Visions entrance.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-951A addressable photoelectric smoke detectors in all electrical rooms, mounted on System Sensor B300A-6 bases.

Modules[edit | edit source]

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.

Former System Specifications (2013-2022)[edit | edit source]

Former System Specifications
FACP: EST iO64
FACP Location: Visions Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 2017?
Year Installed: 2013
Year Decommissioned: 2022

FACP[edit | edit source]

The building was protected by an EST iO64 addressable fire alarm system. The panel was located in the Visions entrance vestibule. The system ran EST’s Signature addressable protocol, and the system coding was temporal.

Annunciators[edit | edit source]

There was an EST RLCD annunciator at the Sofaland entrance.

Notification Appliances[edit | edit source]

Most notification appliances were Edwards “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Sofaland had Edwards G1AVRN horn/strobes (red, wall-mount, no marking, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There were Edwards SIGA-PD addressable photoelectric smoke detectors in all electrical rooms, mounted on EST SIGA-SB bases.

Modules[edit | edit source]

There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

EOLs[edit | edit source]

There were Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.