Revision as of 18:04, 12 January 2025 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS-320C <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: 2015<br />Year Opened: 1966, 1994 |} '''Walmart Supercentre''' is a chain of hypermarkets headquartered in Ben...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2015
Year Opened: 1966, 1994

Walmart Supercentre is a chain of hypermarkets headquartered in Bentonville, Arkansas, USA. This particular store is located at 5004 98 Ave NW, in Edmonton, Alberta, Canada. The store was built in 1966 as Woolworth’s, became Walmart in 1994, and was renovated in 2015. The fire alarm system was upgraded as part of the 2015 renovation.

System Specifications (2015-present)

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors in areas with lower ceilings, mounted on System Sensor B210LPA bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.