Didsbury Community Health Centre

From FireAlarmPedia
Revision as of 15:24, 19 January 2025 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS-320C <br />FACP Location: Electrical Room 117 <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: N/A <br />Year Opened: 2024 |} The '''Didsbury Community Health Centre''' is a health clinic located at 1206 20 Av...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS-320C
FACP Location: Electrical Room 117
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2024

The Didsbury Community Health Centre is a health clinic located at 1206 20 Ave, in Didsbury, Alberta, Canada. The building was built in 2024, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in electrical room 117. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is a Notifier LCD2-80 annunciator paired with a Notifier ACM-24AT annunciator in the main entrance vestibule.

Notification Appliances[edit | edit source]

Most notification appliances are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, set to 15cd).
All washrooms have System Sensor SRLA remote strobes (red, wall-mount, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-951A addressable photoelectric smoke detectors throughout most areas.
There are Notifier FST-951RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the mechanical room and day program kitchen.
All aforementioned detectors are mounted on System Sensor B300A-6 bases.
There are System Sensor “Innovair Flex” D2A conventional photoelectric duct smoke detectors on all air handling units.

Modules[edit | edit source]

There are Notifier FDM-1A addressable dual-input monitor modules supervising the duct smoke detectors and dampers.
There are Notifier FRM-1A addressable relay modules for fan and damper control.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all conventional and signal circuits.