Stanton Territorial Hospital

From FireAlarmPedia
Revision as of 16:51, 8 February 2025 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Edwards EST3 <br />FACP Location: Various <br />System Type: Two-Stage Networked Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70VRMS (audible) <br> 24VDC (visual) <br />System Coding: 20BPM (alert) <br> Temporal (alarm) <br>Strobes Synchronized: Yes, Genesis <br />Date of last known Upgrade: N/A <br />Year Opened: 2018 |} '''Stanton Territorial Hospital''' is a h...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST3
FACP Location: Various
System Type: Two-Stage Networked Addressable
System Line Voltage: 120VAC
NAC Voltage: 70VRMS (audible)
24VDC (visual)
System Coding: 20BPM (alert)
Temporal (alarm)
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2018

Stanton Territorial Hospital is a hospital located at 548 Byrne Road, Yellowknife, Northwest Territories, Canada. It is the largest hospital in the Northwest Territories and has 100 beds. It was built in 2018, and the fire alarm system is original.

System Specifications (2018-present)

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The system is a network consisting of many nodes, the panels are located in the entrance and some electrical rooms. The system runs Edwards’ Signature addressable protocol, and is equipped with voice-evacuation. The system is configured for two-stage operation. The alert signal is a 20BPM chime, and the alarm signal is a temporal 1kHz tone. Live “Code Red” announcements are made by security in lieu of voice messages. The general alarm timer length is 3.5 minutes.

Annunciators

There are Edwards EST3-LCDANN annunciators with the LCDXL1 displays in all nurses’ stations.

Booster Panels

There are Edwards BPS6A 6-amp booster power supplies on the system.

Notification Appliances

All notification appliances are from Edwards’ “Genesis” line of products.
Most notification appliances are Edwards GC-S7VM speaker/strobes (white, ceiling-mount, no marking, set to 30cd).
Areas requiring more audible coverage have Edwards GC-S7 speakers (white, ceiling-mount, no marking).
Some areas have Edwards G4-S7VM speaker/strobes (white, wall-mount, no marking, set to 15cd).
All washrooms have Edwards G1-VM remote strobes (white, wall-mount, no marking, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building.
Some areas have Edwards SIGA-PD addressable photoelectric smoke detectors.
Certain areas have EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors
All air handling units have EST “SuperDuct” SIGA-SD addressable photoelectric duct smoke detectors.
The boiler room has a System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detector, wired to an EST SIGA-CT1 addressable monitor module.

Modules

There are EST SIGA-CT1 and SIGA-CT2 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes
There are EST SIGA-CC1 addressable control modules to trigger the boosters..
There are EST SIGA-IM isolator modules on each SLC.

Firefighter’s Telephones

There are Edwards 6833-4 firefighter’s telephones on each floor.

EOLs

There are Edwards EOL-P1 on the conventional heat detector circuit and all sprinkler and signal circuits.