| System Specifications |
|---|
| FACP: None System Type: 120V Hardwired System Line Voltage: 120VAC System Coding: Continuous Date of last known Upgrade: 1978 Year Opened: 1953 |
The Mayfield Building is a small office building located at 1134 8 Ave SW, in Calgary, Alberta, Canada. The building was built in 1953, and the fire alarm system was installed in 1978. Parts have been replaced as deficiencies occur.
System Specifications (1978-present)
FACP
The building is protected by a 120V hardwired fire alarm system, with bells and initiating devices wired in series. The system coding is continuous.
Notification Appliances
All notification appliances are Edwards "Adaptabel" 326D vibrating bells (6" gong).
Initiating Devices
Pull Stations
All pull stations are Edwards 270-SPO conventional single-action pull stations.
Automatic Detection Devices
There are FDD CR-135 conventional 135°F fixed-temperature/rate-of-rise heat detectors in all storage rooms.
There is a System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detector in the janitor room, and a System Sensor 5604A conventional 194°F fixed-temperature heat detector in the boiler room.