Calgary Chinese Pentecostal Church

From FireAlarmPedia
Revision as of 18:50, 14 March 2025 by Alberta Fire Alarms (talk | contribs) (Created page with " {| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Mircom FA-1000 <br />FACP Location: Main Lobby <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2014-15 <br />Year Opened: 1978 |} The '''Calgary Chinese Pentecostal Church''' is a church located at 127 2 Ave SE, in the Chinatown distr...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Mircom FA-1000
FACP Location: Main Lobby
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: 2014-15
Year Opened: 1978

The Calgary Chinese Pentecostal Church is a church located at 127 2 Ave SE, in the Chinatown district of Calgary, Alberta, Canada. The church was built in 1978, and the fire alarm system was upgraded in the 1990s, with a partial upgrade occurring between 2014 and 2015.

System Specifications (2015-present)

FACP

The building is protected by a Mircom FA-1000 conventional fire alarm system. The panel is located in the main lobby. The system coding is temporal.

Notification Appliances

All notification appliances are Mircom "Select-A-Horn/Strobe" FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).

Initiating Devices

Pull Stations

Most pull stations are Cerberus MS-151B conventional single-action pull stations.
There are Edwards 270-SPOW conventional single-action pull stations in the basement as deficiency replacements.
There is an Edwards 274-101 conventional single-action pull station at the top of the west stairs, likely remaining from the original system.
There is a Mircom MS-401 conventional single-action pull station in the rec room as a deficiency replacement.

Automatic Detection Devices

There are System Sensor C2W-BA conventional photoelectric smoke detectors at the top of each stairwell, and in the chapel baby room.
There are FDD CR-135 conventional 135°F fixed-temperature/rate-of-rise heat detectors throughout the basement, and in all furnace, storage, mechanical and electrical rooms.
There is a System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detector in the west chapel balcony.
There are two Edwards 284B-PL conventional 194°F fixed-temperature heat detectors in the kitchen.

EOLs

There are a mix of Cerberus EL-30, Edwards EOL-P1 and Mircom MP-300 end of line resistor plates on all circuits.