Willow Lodge N2

From FireAlarmPedia
Revision as of 21:24, 12 May 2025 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Mircom FA-1000 <br />FACP Location: Centre Hallway Exit <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, Mircom <br />Date of last known Upgrade: N/A <br />Most Recent Known Modification: 2023, FACP <br /> Year Opened: 1990s |} '''Willow Lodge''' is a Suncor camp loca...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Mircom FA-1000
FACP Location: Centre Hallway Exit
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Mircom
Date of last known Upgrade: N/A
Most Recent Known Modification: 2023, FACP
Year Opened: 1990s

Willow Lodge is a Suncor camp located in Wood Buffalo, Alberta, Canada. This page will cover Building N2, which is a dormitory building. The building was built in the 1990s, and the fire alarm system was mostly upgraded in the 2010s, with an FACP replacement occurring in 2023.

System Specifications

FACP

The building is protected by a Mircom FA-1000 conventional fire alarm system. The panel is located at the centre hallway exit. The system coding is temporal.

Notification Appliances

All common areas have Mircom "Select-A-Horn/Strobe" FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).
All dorm rooms have Mircom FS-400-RR remote strobes (red, wall-mount, set to 15cd) paired with Mircom MH-S25WA silenceable mini-horns (white).

Initiating Devices

Pull Stations

Most pull stations are Edwards 270-SPO conventional single-action pull stations.
There is a Mircom MS-401 conventional single-action pull station by the rear exit as a deficiency replacement.

Automatic Detection Devices

There are Edwards 245A conventional 135°F fixed-temperature heat detectors in most dorm and service rooms.
Some aforementioned rooms have System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors as deficiency replacements.
There are Edwards 284B-PL conventional 194°F fixed-temperature heat detectors in all water heater and laundry rooms.
There are System Sensor C2W-BA conventional photoelectric smoke detectors throughout all common areas.

Modules

There is a Mircom MIX-4050 sync module synchronizing all strobes.

EOLs

There are Mircom MP-300 end of line resistor plates on all circuits.