Revision as of 23:12, 31 May 2025 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS2-640C<br />FACP Location: Main Entrance Vestibule<br />System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC<br />System Coding: Temporal<br>Strobes Synchronized: Yes, System Sensor<br />Date of last known Upgrade: N/A<br />Most Recent Known Modification: 2010s, Some smokes<br /> Year Opened: 2008 |} '''KBL Projects''' is an env...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS2-640C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Most Recent Known Modification: 2010s, Some smokes
Year Opened: 2008

KBL Projects is an environmental health service located at 10501 Barlow Tr SE, Calgary, Alberta. This page will cover the main building. It was built in 2008, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
This panel is part of KBL's NOTI-FIRE-NET network, and is networked to the other two buildings on site; this panel is equipped with an NCA-2 display.

Notification Appliances

All notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.

Automatic Detection Devices

There are Notifier FSI-851A addressable ionization smoke detectors at the top of most stairwells.
There are Notifier FSP-851A addressable photoelectric smoke detectors at the top of all other stairwells as deficiency replacements.
There is a Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detector in the electrical room.
All detectors are mounted on Notifier B710LPA bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits but one; the remaining signal circuit is equipped with a Simplex 2081-9040C end of line resistor plate.