| System Specifications |
|---|
| FACP: Edwards EST3 FACP Location: Security Office System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (alert) Temporal (Alarm) Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 1999 Most Recent Known Modification: 2010s (strobes) Year Opened: 1972 |
Scarborough Town Centre is a shopping mall located at 300 Borough Dr, Scarborough, Ontario, Canada. The mall is managed by Oxford Properties. The mall opened in 1973, and was extensively renovated from 1998-1999. The fire alarm system was upgraded in 1999.
System Specifications
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the security office. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, followed by temporal for the alarm signal.
Booster Panels
There are multiple Edwards BPS6A 6-amp booster power supplies throughout the building.
Notification Appliances
Most notification appliances are General Signal MB10-24 motor bells (10" gong).
Some areas have Edwards MB6-24 motor bells (6" gong).
There are some Edwards MB10-24 motor bells (10" gong) as deficiency replacements.
Most bells are mounted behind grilles.
There are Edwards "Genesis" G1R-VM remote strobes (red, wall-mount, no marking, set to 15cd) in some areas.
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors in some areas, mounted on EST SIGA-SB bases.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches, kitchen suppression systems, generator run and trouble, plus the fire pump's contacts.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM isolator modules on the SLC.
There are EST SIGA-CC1 addressable control modules for triggering the boosters.
EOLs
There are Edwards EOL-P1 end-of-line resistor plates on all monitor-module supervised and signal circuits.