Cedars of Calgary Building F

From FireAlarmPedia
Revision as of 20:56, 16 June 2025 by TwentyThree33 (talk | contribs) (Created page with " {| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Edwards FireShield Plus FSP302G<br />FACP Location: F1 Electrical Room<br />System Type: Single-Stage Conventional<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR<br />System Coding: Temporal<br>Strobes Synchronized: Yes, Genesis<br />Date of last known Upgrade: 2018<br />Most Recent Known Modification: N/A<br />Year Opened: 1977 |} '''Cedars of Calgary''' is an apartmen...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards FireShield Plus FSP302G
FACP Location: F1 Electrical Room
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 2018
Most Recent Known Modification: N/A
Year Opened: 1977

Cedars of Calgary is an apartment complex located at 215 86 Ave SE, in Calgary, Alberta, Canada. The complex is owned and operated by Shelter Canadian Properties. This page will cover Building F, which was built in 1977. The fire alarm system was partially upgraded in 2018.

System Specifications (2018-present)

FACP

The building is protected by an Edwards FireShield Plus FSP302G conventional fire alarm system. The panel is located in the F1 electrical room. The system coding is temporal.
This panel replaced an Edwards 1523.

Annunciators

There is an Edwards FSRSI annunciator equipped with an FSRZI-A module outside the F1 west entrance.

Notification Appliances

All indoor notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd) mounted on Edwards G1TR trim plates.
For outdoor notification, there is an Edwards WG4RF-H weatherproof remote horn (red, FIRE marking) outside the F1 entrance.

Initiating Devices

Pull Stations

All pull stations but one are Edwards 270-SPO conventional single-action pull stations.
There is a Notifier NFM-950B conventional single-action pull station in the F2 first floor corridor as a deficiency replacement.

Automatic Detection Devices

There are System Sensor C2W-BA conventional photoelectric smoke detectors in all corridors.
There are Potter CF-135W conventional 135°F fixed-temperature heat detectors in all mechanical and electrical rooms.
There are System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors at the top of each stairwell.
There are Edwards 284A conventional 194°F fixed-temperature heat detectors in all laundry rooms.

EOLs

All end of line resistors are in field devices.