Cedars of Calgary Building K

From FireAlarmPedia
Revision as of 20:58, 16 June 2025 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Mircom FA-1025T<br />FACP Location: K2 Electrical Room<br />System Type: Single-Stage Conventional<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR<br />System Coding: Temporal<br>Strobes Synchronized: N/A<br />Date of last known Upgrade: N/A<br />Most Recent Known Modification: 2010s, Smokes<br />Year Opened: 1977 |} '''Cedars of Calgary''' is an apartment complex located...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Mircom FA-1025T
FACP Location: K2 Electrical Room
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: N/A
Date of last known Upgrade: N/A
Most Recent Known Modification: 2010s, Smokes
Year Opened: 1977

Cedars of Calgary is an apartment complex located at 215 86 Ave SE, in Calgary, Alberta, Canada. The complex is owned and operated by Shelter Canadian Properties. This page will cover Building K, which was built in 1977. The fire alarm system is mostly original, with devices replaced as deficiencies occur.

System Specifications

FACP

The building is protected by a Mircom FA-1025T conventional fire alarm system. The panel is located in the K2 electrical room. The system coding is temporal.
This panel replaced an Edwards 1523 in the 2000s.

Annunciators

There is a Mircom RA-105 annunciator outside the K2 entrance.

Notification Appliances

All indoor notification appliances but one are Edwards "Durabel" 6100D vibrating bells (6" gong).
There is one Mircom BL-10A motor bell (10" gong) as a deficiency replacement.
For outdoor notification, there is a Mircom BL-6B motor bell (6" gong) paired with a beacon outside the K2 entrance.

Initiating Devices

Pull Stations

Most pull stations are Edwards 270-SPO conventional single-action pull stations.
Some areas have Mircom MS-401 conventional single-action pull stations as deficiency replacements.

Automatic Detection Devices

There are System Sensor C2W-BA conventional photoelectric smoke detectors throughout all corridors.
There are System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors at the top of each stairwell.
There are Mirtone 73330 conventional 135°F fixed-temperature heat detectors in all laundry rooms.
There are Potter CF-135W conventional 135°F fixed-temperature heat detectors in all electrical and mechanical rooms.

EOLs

All end of line resistors are located in field devices.