1835 27 Ave SW, Calgary, AB

From FireAlarmPedia
Revision as of 22:04, 16 June 2025 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Mircom FA-1025T<br />FACP Location: Manager's Office<br />System Type: Single-Stage Conventional<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR<br />System Coding: Temporal<br>Strobes Synchronized: No<br />Date of last known Upgrade: 2003<br />Most Recent Known Modification: 2010s, FACP<br />Year Opened: 1961 |} '''1835 27 Ave SW''' is the address of a halfway house in C...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Mircom FA-1025T
FACP Location: Manager's Office
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: 2003
Most Recent Known Modification: 2010s, FACP
Year Opened: 1961

1835 27 Ave SW is the address of a halfway house in Calgary, Alberta, Canada. The building was built in 1961, and the fire alarm system was upgraded in 2003.

System Specifications (2003-present)

FACP

The building is protected by a Mircom FA-1025T conventional fire alarm system. The panel is located in the manager's office. The system coding is temporal.

Annunciators

There is a Mircom RA-105 annunciator in the main entrance vestibule.

Notification Appliances

All notification appliances are System Sensor "SpectrAlert" P1224MCA horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Notifier NFM-950B conventional single-action pull stations.

Automatic Detection Devices

There are System Sensor C2W-BA conventional photoelectric smoke detectors in all bedrooms, throughout most corridors and at the top of each stairwell.
There are Mirtone 73330 conventional 135°F fixed-temperature heat detectors in the dining room and some other rooms.
There are the following heat detectors installed in the building: System Sensor 5601A in dining room
System Sensor 5603A in laundry room
System Sensor 5604A in boiler room
FDD CR-135 in food storage room
Potter FR-135W in main floor furnace room

EOLs

There are Mircom MP-300 end of line resistor plates on all circuits.