Revision as of 14:05, 4 August 2025 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Edwards EST3<br />FACP Location: Various<br />System Type: Two-Stage Networked Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible)<br>24VDC (Visual)<br />System Coding: 20BPM Tone (Alert)<br>Slow Whoop (Alarm)<br>Strobes Synchronized: Yes, EST<br />Date of last known Upgrade: 2000s<br />Most Recent Known Modification: N/A<br />Year Opened: 1990s |} '...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST3
FACP Location: Various
System Type: Two-Stage Networked Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: 20BPM Tone (Alert)
Slow Whoop (Alarm)
Strobes Synchronized: Yes, EST
Date of last known Upgrade: 2000s
Most Recent Known Modification: N/A
Year Opened: 1990s


Secure Building SB00001 is a secure facility added to Fire Alarmpedia under the Secure Building Information System.


System Specifications

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. This is a networked system with 6 nodes; node locations will not be disclosed. The system runs Edwards’ Signature addressable protocol, is equipped with voice evacuation, and is configured for two-stage operation. The alert signal is a 20BPM tone, and the alarm signal is slow whoop.


FACP Accessories

There are two EST FireWorks workstations on the system.


Notification Appliances

Most notification appliances are Edwards 965-1A-8RW remote speakers (white, 8” round, 70V).
Electrical and mechanical rooms have Edwards 965-6A-8RW speaker/strobes (white, 8” round, 70V, 15/75cd).
The main electrical room has an Edwards “Integrity” 757-1A-R70 remote speaker (red, 70V).


Initiating Devices

Pull Stations

Staff and service areas have EST SIGA-270P addressable two-stage single-action pull stations.
All other areas have custom Edwards/General Signal keyswitch stations.


Automatic Detection Devices

There are a mix of the following addressable smoke detectors throughout all areas: EST SIGA-IPHS, SIGA-PS, SIGA-PD, SIGA-OSD.
All detectors are mounted on EST SIGA-SB bases.


Modules

There are EST SIGA-CT1 addressable monitor modules supervising several system components.
There are EST SIGA-CR addressable relay modules, the purpose of which will not be disclosed.


EOLs

There are Edwards EOL-P1 end of line resistor plates on all monitored and signal circuits.


Sequence of Operation

A first stage alarm will sound 20BPM tones in the common corridors throughout, and the living areas near the alarm. A second stage alarm will sound a slow whoop tone throughout the facility.