| System Specifications |
|---|
| FACP: Edwards EST3 FACP Location: Various System Type: Two-Stage Networked Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: Unknown Strobes Synchronized: Yes, Genesis Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2019 |
Brookfield Residential YMCA at Seton is a recreation centre located at 4995 Market St SE, in Calgary, Alberta, Canada. The facility is the world's largest YMCA. The building was built in 2019, and the fire alarm system is original.
System Specifications
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. This is a networked system with 2 nodes: Node 1 is located in the back-of-house CACF room, and Node 2 is located in the southwest entrance vestibule. The system runs Edwards' Signature addressable protocol, is equipped with voice evacuation, and is configured for two-stage operation. The messages and/or tones are unknown at this time.
Notification Appliances
Most notification appliances are Edwards "Genesis" G4-S7VM speaker/strobes (white, wall-mount, no marking, 70V, set to 15cd).
Some areas have Edwards GC-S7VM speaker/strobes (white, ceiling-mount, no marking, 70V, set to 15cd).
For outdoor notification, there is an Edwards CS405-7A-T weatherproof remote strobe (red, wall-mount, 15/75cd) outside the southwest entrance.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices
There are Edwards SIGA-PD addressable photoelectric smoke detectors at the top of each stairwell, in the pool area by the divider doors, in all elevator lobbies, and in some other areas.
There are likely Edwards SIGA-HRD addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
All aforementioned detectors are mounted on EST SIGA-SB bases.
There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on all air handling units.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.