Days Inn by Wyndham Vermilion

From FireAlarmPedia
Revision as of 15:46, 24 August 2025 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards 2280
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Date of last known Upgrade: 1978
Year Opened: 1906

Days Inn is a chain of budget hotels owned by Wyndham. The chain is headquartered in Parsippany, New Jersey, USA, and has locations worldwide. This particular hotel is located at 4807 51 St, Vermilion, Alberta, Canada. The hotel was built in 1906 as the Brunswick Hotel, and was expanded in 1978 as the Brunswick Motor Inn. The fire alarm system was installed in 1978, with parts replaced as deficiencies occur.

System Specifications (1978-present)

FACP

The building is protected by an Edwards 2280 conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is continuous.

Notification Appliances

Most notification appliances are Edwards "Durabel" 6100D vibrating bells (10" gong).
The second floor has Edwards 439D-10AWC vibrating bells (10" gong), installed around 1993.

Initiating Devices

Pull Stations

All pull stations but one are Edwards 270-SPO conventional single-action pull stations.
There is one Edwards CCS-642 conventional single-action pull station in the Aria restaurant.

Automatic Detection Devices

The upper floor has Edwards 6350B conventional ionization smoke detectors.
There are System Sensor C2W-BA conventional photoelectric smoke detectors as deficiency replacements.
The Aria restaurant has Edwards 241 conventional 135°F fixed-temperature/rate-of-rise heat detectors.
There is a System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detector in that area as a deficiency replacement.
There is an FDD CR-135W conventional 135°F fixed-temperature/rate-of-rise heat detector by the front desk.