System Specifications
FACP: Notifier NFS-320C
FACP Location: Electrical Room 117
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2024

The Didsbury Community Health Centre is a health clinic located at 1206 20 Ave, in Didsbury, Alberta, Canada. The building was built in 2024, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in electrical room 117. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Annunciators

There is a Notifier LCD2-80 annunciator paired with a Notifier ACM-24AT annunciator in the main entrance vestibule.

Notification Appliances

Most notification appliances are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, set to 15cd).
All washrooms have System Sensor SRLA remote strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-951A addressable photoelectric smoke detectors throughout most areas.
There are Notifier FST-951RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the mechanical room and day program kitchen.
All aforementioned detectors are mounted on System Sensor B300A-6 bases.
There are System Sensor “Innovair Flex” D2A conventional photoelectric duct smoke detectors on all air handling units.

Modules

There are Notifier FDM-1A addressable dual-input monitor modules supervising the duct smoke detectors and dampers.
There are Notifier FRM-1A addressable relay modules for fan and damper control.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end of line resistor plates on all conventional and signal circuits.