Revision as of 20:12, 3 September 2025 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Mircom FX-2000<br />FACP Location: Main Electrical Room<br />System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR<br />System Coding: Temporal<br>Strobes Synchronized: No<br />Date of last known Upgrade: N/A<br />Most Recent Known Modification: N/A<br />Year Opened: 2010s |} '''Secure Building SB00002''' is a secure facility added under Fi...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Mircom FX-2000
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2010s

Secure Building SB00002 is a secure facility added under Fire Alarmpedia's Secure Buildings Information Program.

System Specifications

FACP

The facility is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main electrical room. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.

Annunciators

There is a Mircom RAX-LCD annunciator paired with a Mircom RAX-1048TZDS annunciator in the main entrance vestibule. Both annunciators are mounted in a Mircom BB-1002 enclosure.

Notification Appliances

All notification appliances are Mircom "Select-A-Horn/Strobe" FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).

Initiating Devices

Pull Stations

All pull stations are Mircom MS-401AD addressable single-action pull stations.

Automatic Detection Devices

There are Mircom MIX-2251APA addressable photoelectric smoke detectors in some areas.
There are Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
All detectors are mounted on System Sensor B210LPA bases.

Modules

There are Mircom MIX-M500MAPA addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Mircom MIX-M500RAPA addressable relay modules serving various purposes.
There are System Sensor M500XA isolator modules on the SLC.

EOLs

There are Mircom MP-300 end of line resistor plates on all sprinkler and signal circuits.