| System Specifications |
|---|
| FACP: Notifier NFS-320C FACP Location: Main Mechanical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2019 |
10555 74 St SE is the address of a small industrial plaza in the Point Trotter Industrial district of Calgary, Alberta, Canada. The building was built in 2019, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main mechanical room. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances
Most notification appliances are System Sensor "L-Series" P2RLA horn/strobes (red, wall-mount, bilingual lettering, set to 15cd).
There are System Sensor PC2RLA horn/strobes (red, ceiling-mount, bilingual lettering, set to 15cd) in the warehouse areas of Units 120 and 130.
There are System Sensor SGRLA remote strobes (red, wall-mount, small-footprint, bilingual lettering, set to 15cd) in all washrooms.
There is a System Sensor "SpectrAlert Advance" P2RA horn/strobe (red, wall-mount, set to 15cd) in the Unit 110 warehouse, likely new old stock.
For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the main mechanical room.
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors at the top of each stairwell, in the server and janitor rooms of Unit 110, and in the main electrical room.
There is a Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detector in the main mechanical room.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There is a Notifier FSP-951A addressable photoelectric smoke detector in the server room of Unit 130, mounted on a System Sensor B300A-6 base.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier ISO-XA isolator modules on the SLC.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.