| System Specifications |
|---|
| FACP: Notifier NFS2-3030C FACP Location: CACF Room System Type: Single-Stage Hybrid-Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: Temporal "Air Horn" Tone Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2022 Most Recent Known Modification: N/A Year Opened: 1972 |
Hull Estates is an apartment tower located at 1200 6 St SW, in Calgary, Alberta, Canada. The building was built in 1972, and the fire alarm system was partially upgraded in 2022.
System Specifications (2022-present)
Please note that some system details may not be accurate, as information is based on memory from 2023. This page should not be used for official purposes.
FACP
The building is protected by a Notifier NFS2-3030C hybrid-addressable fire alarm system. The panel is located in the CACF room on the main floor, with a zone cabinet located in the basement electrical room. The system runs Notifier's FlashScan addressable protocol, and is equipped with Notifier's "Digital Voice Command" voice evacuation system. The evacuation signal is a temporal "air horn" tone; the system does not play a pre-recorded message.
This panel replaced a Notifier NFS2-3030C without DVC, which replaced a Notifier System 5000, which in turn replaced the original FACP, an Edwards Custom 6500.
Annunciators
There is a Notifier LCD-160 annunciator in the main entrance vestibule.
Booster Panels
There is a Notifier ACPS-610 addressable booster power supply in the electrical room on the 20th floor.
Notification Appliances
All notification appliances are System Sensor "L-Series" SPSCWLA speaker/strobes (white, ceiling-mount, bilingual lettering, set to 70V/15cd).
Initiating Devices
Pull Stations
Most pull stations are Edwards 270-SPO conventional single-action pull stations.
Some areas have Notifier MPS-950B conventional single-action pull stations as deficiency replacements.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout all floors excluding main and 28, and in the elevator lobbies on each floor.
There is a Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detector at the top of the elevator shaft.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There is a Notifier FSP-951A addressable photoelectric smoke detector in the CACF room, mounted on a System Sensor B300A-6 base.
There are FDD CR-135 conventional 135°F fixed-temperature/rate-of-rise heat detectors in the garbage rooms on each floor.
There are System Sensor C2W-BA conventional photoelectric smoke detectors throughout the main and 28th floors.
There are duct smoke detectors on the system however their specifications are unknown.
Firefighter's Telephones
There are Notifier FT-301A fire phones at each stairwell on each floor, controlled via Notifier FTM-1A fire phone modules.
EOLs
There are Notifier EOL-CR end of line resistor plates on all conventional and signal circuits.