Revision as of 22:11, 14 December 2025 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS-320C<br />FACP Location: Main Electrical Room<br />System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC<br />System Coding: Temporal<br>Strobes Synchronized: Yes, System Sensor<br />Date of last known Upgrade: 2010s<br />Most Recent Known Modification: N/A<br />Year Opened: 1997 |} '''Watermania''' is a waterpark and aquatic ce...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2010s
Most Recent Known Modification: N/A
Year Opened: 1997

Watermania is a waterpark and aquatic centre located at 14300 Entertainment Blvd, in Richmond, British Columbia, Canada. The building was built in 1997, and the fire alarm system was upgraded in the 2010s.

System Specifications (2010s-present)

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Annunciators

There is a Matrix custom graphic annunciator outside the sports therapy entrance, driven by a Notifier LDM-32 lamp driver module.

Notification Appliances

All notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors at the top of each stairwell, mounted on System Sensor B210LPA bases.
There is a System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detector in the wave generation room, wired to a Notifier FMM-101A addressable monitor module.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.