| System Specifications |
|---|
| FACP: Edwards iO1000 FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR (FACP) 24VDC (Booster) System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2020 Most Recent Known Modification: N/A Year Opened: 2001 |
Walmart Supercentre is a chain of hypermarkets with locations across North America. This particular store is located at 860 Langford Parkway, in Langford, British Columbia, Canada. The store was built in 2001, and was renovated in 2020. The fire alarm system was upgraded as part of the 2020 renovation.
System Specifications (2020-present)
FACP
The building is protected by an Edwards iO1000 addressable fire alarm system. The panel location is unknown. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.
Annunciators
There are Edwards RLCD-C annunciators paired with Edwards RLED24 annunciators in the main entrance vestibule and outside the main entrance.
The vestibule annunciators are mounted in an Edwards RA-ENC2 enclosure.
Booster Panels
There are Edwards BPS6AC 6-amp booster power supplies on the system.
Notification Appliances
Most notification appliances are Edwards "Genesis" G4AVRF horn/strobes (red, wall-mount, FIRE marking, set to 15cd).
The storefront has Edwards G4VRF remote strobes (red, wall-mount, FIRE marking, set to 15cd) for additional visual coverage.
Throughout the store, horn/strobes and strobes are mounted on pillars in an alternating pattern on all four sides.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
None noticed.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the kitchen suppression system, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-CC1 addressable control modules triggering all booster panels.
There are EST SIGA-IM addressable isolator modules on the SLC.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all kitchen suppression, sprinkler and signal circuits.