More actions
| System Specifications |
|---|
| FACP: Simplex 4007ES FACP Location: Main Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, SmartSync Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2015 |
McDonald's is a multinational chain of fast food restaurants. This particular restaurant is located at 854 Langford Parkway, in Langford, British Columbia, Canada. The restaurant was built in 2015, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located in the main electrical room. The system runs Simplex's IDNet addressable protocol, and the system coding is temporal.
Annunciators
There is a Simplex 4606-9202 annunciator outside the main electrical room.
Notification Appliances
Most notification appliances are Simplex "TrueAlert" 4906-9129 horn/strobes (white, wall-mount, set to 15cd).
Some areas have Simplex 4906-9103 remote strobes (white, wall-mount, set to 15cd).
For outdoor notification, there is a Simplex 4906-9131 weatherproof horn/strobe (red) outside the main electrical room.
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex "TrueAlarm" 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors throughout the building, mounted on Simplex 4098-9792 bases.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising the kitchen suppression systems, and the sprinkler system's tamper and flow switches.
There are Simplex 4090-9116 addressable isolator modules on the SLC.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all kitchen suppression, sprinkler and signal circuits.