Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Mail is now working! Feel free to request an account. Accounts are available to invested enthusiasts/technicians in the industry. :)

La Crete Inn & Suites

From FireAlarmPedia
Revision as of 22:04, 18 December 2025 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications (Main Building) |- | |- | FACP: EST FireShield FS502G<br />FACP Location: Behind Front Desk<br />System Type: Single-Stage Conventional<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR<br />System Coding: Continuous<br>Strobes Synchronized: Yes, Self-Sync<br />Date of last known Upgrade: N/A<br />Most Recent Known Modification: N/A<br />Year Opened: 2005 |} '''La Crete Inn & Suites''' is...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications (Main Building)
FACP: EST FireShield FS502G
FACP Location: Behind Front Desk
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Strobes Synchronized: Yes, Self-Sync
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2005

La Crete Inn & Suites is an independent hotel located at 10101 101 St, in La Crete, Alberta, Canada. The hotel consists of 2 buildings. The main building was built in 2005, and Building 3 was built in 2011. The fire alarm systems are original to both buildings.

System Specifications (Main Building)

FACP

The building is protected by an EST FireShield FS502G conventional fire alarm system. The panel is located behind the front desk. The system coding is continuous.

Notification Appliances

Most notification appliances are Edwards 439D-6AWC vibrating bells (6" gong) mounted on Edwards 403-5A-R strobe plates (15cd).
The lobby has Edwards 439D-10AWC vibrating bells (10" gong) mounted on Edwards 403-5A-R strobe plates (15cd).

Initiating Devices

Pull Stations

All pull stations are Edwards 270-SPO conventional single-action pull stations.

Automatic Detection Devices

There are System Sensor 1400A conventional ionization smoke detectors throughout the main floor.
There are Edwards EC30U-3 conventional photoelectric smoke detectors throughout the second floor.
There are Edwards 281B-PL conventional 135°F fixed-temperature/rate-of-rise heat detectors in some rooms and at the top of each stairwell.
There is an Edwards 284B-PL conventional 194°F fixed-temperature heat detector in the laundry room.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all circuits.

System Specifications (Building 3)

System Specifications
FACP: Mircom FX-2000
FACP Location: Central Stairwell
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Mircom
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2011

FACP

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the central stairwell. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.

Notification Appliances

All common areas have Mircom "Select-A-Horn/Strobe" FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).
All guest rooms have Mircom MH-S25WA silenceable mini-horns (white).

Initiating Devices

Pull Stations

All pull stations are Mircom MS-401AD addressable single-action pull stations.

Automatic Detection Devices

There are Mircom MIX-2251BA addressable photoelectric smoke detectors throughout all common areas.
There are Mircom MIX-5251HA addressable 190°F fixed-temperature heat detectors in the laundry room.
All detectors are mounted on System Sensor B210LPA bases.

EOLs

There are Mircom MP-300 end of line resistor plates on all signal circuits.