| System Specifications |
|---|
| FACP: Edwards iO1000 FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2024 Most Recent Known Modification: N/A Year Opened: 1914 |
CPKC is a railway headquartered in Calgary, Alberta. This page will cover Building 6 of the Ogden Campus, which is the primary training centre for new recruits. The building is located at 7550 Ogden Dale Road SE, in Calgary, Alberta, Canada. The building was built in 1914, and was renovated in the 2010s. The fire alarm system was upgraded in 2024.
System Specifications (2024-present)
FACP
The building is protected by an Edwards iO1000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.
Notification Appliances
Most notification appliances are Edwards "Genesis" G1AVRF horn/strobes (red, wall-mount, FIRE marking, set to 15cd).
Some areas have Edwards G1ARF remote horns (red, wall-mount, FIRE marking).
All notification appliances are mounted on Edwards G1TR trim plates (red, no marking).
Initiating Devices
Pull Stations
All pull stations are Edwards SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There is an Edwards SIGA-OSD addressable optical smoke detector at the top of the mezzanine stairwell, mounted on an Edwards SIGA-SB base.
Modules
There are Edwards SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Edwards SIGA-CR addressable relay modules for AHU shutdown.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.
Former System Specifications (2000s-2024)
| Former System Specifications |
|---|
| FACP: Siemens FireFinder XLS FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, Siemens Most Recent Known Modification: N/A Year Installed: 2000s Year + Reason Decommissioned: 2024, Issues with FACP |
FACP
The building was protected by a Siemens FireFinder XLS addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran Siemens' FirePrint addressable protocol, and the system coding was temporal.
Notification Appliances
Most notification appliances were Siemens U-MMT-MCS horn/strobes (red, wall-mount, set to horn/15cd).
Some areas had Siemens U-MMT remote horns (red, set to horn).
Initiating Devices
Pull Stations
All pull stations were Siemens HMS-S addressable single-action pull stations.
Automatic Detection Devices
There was a Siemens HFP-11 addressable multisensor smoke/heat detector at the top of the mezzanine stairwell, mounted on a Siemens DB-11 base.
Modules
There were Siemens HTRI-S addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There were Siemens HTRI-R addressable relay modules for AHU shutdown.
EOLs
There were Siemens EL-300C end of line resistor plates on all sprinkler and signal circuits.