More actions
| System Specifications |
|---|
| FACP: Notifier NFS-320C FACP Location: Main Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2023 |
Blackmud Creek Industrial Estates is an industrial park located in Nisku, Alberta, Canada. This page will cover Building E, located at 2305 9 Street. The building was built in 2023, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Booster Panels
There are Notifier PSE-6C 6-amp booster power supplies in two units.
Notification Appliances
Most notification appliances are System Sensor "L-Series" P2RLA-E horn/strobes (red, wall-mount, set to 15cd).
One washroom has a System Sensor SRLA-E remote strobe (red, wall-mount, set to 15cd).
Polywest has System Sensor P2WLED-B horn/strobes (white, wall-mount, set to 15cd) and SWLED-B remote strobes (white, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor "SpectrAlert Advance" P2RA horn/strobe (red, wall-mount, set to 15cd) outside the electrical room.
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-951A addressable photoelectric smoke detectors in some units.
There are Notifier FST-951A addressable 135°F fixed-temperature heat detectors in all electrical rooms.
All detectors are mounted on System Sensor B300A-6 bases.
Modules
There are Notifier FDM-1A addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.