| System Specifications |
|---|
| FACP: Notifier NFS2-3030C FACP Location: Various System Type: Single-Stage Networked Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2015 |
Canadian Natural Resources Ltd is an oil and gas production company. This page will cover the Pike Lodge, a workers' camp located near Conklin, Alberta, Canada. The camp was built in 2015, and the fire alarm systems are original.
Please note that the system is a Notifier NOTI-FIRE-NET network, and was constructed all as one building.
System Specifications (Main Lodge)
FACP
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the utility room. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Annunciators
There is a Notifier NCA-2C annunciator paired with a custom graphic in the main entrance vestibule.
Booster Panels
There are Notifier ACPS-610 power supplies throughout.
Notification Appliances
Most notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
Some areas have System Sensor PC2WA horn/strobes (white, ceiling-mount, set to 15cd).
The washrooms have System Sensor SRA remote strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside.
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors in most areas.
There are Notifier FST-851A addressable 135°F fixed-temperature heat detectors in areas such as janitor rooms.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There are System Sensor "Innovair Flex" DNRA duct smoke detector housings equipped with Notifier FSP-851A addressable photoelectric heads on all air handling units.
Modules
There are Notifier FDM-1A addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on all SLCs.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.
System Specifications (Dorms)
FACP
The dorms are protected by Notifier NFS2-3030C addressable fire alarm systems. The panels are located in the utility room of each building. The systems run Notifier's FlashScan addressable protocol, and the system coding is temporal for all systems.
Annunciators=
There are Notifier LCD2-80 annunciators paired with Notifier ACM-24AT annunciators at the entrance to each dorm.
Notification Appliances
All notification appliances are System Sensor "SpectrAlert Advance" PC2WA horn/strobes (white, ceiling-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSI-851A addressable ionization smoke detectors throughout all common areas.
There are Notifier FSP-851A addressable photoelectric smoke detectors in each dorm room.
All common area detectors are mounted on System Sensor B210LPA bases, while all dorm room detectors are mounted on System Sensor B200SRA sounder bases.
Modules
There are Notifier FDM-1A addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on all SLCs.
EOLs
There are a mix of Notifier EOL-CR, Edwards EOL-P1 and Mircom MP-300 end of line resistor plates on all sprinkler and signal circuits.