| System Specifications |
|---|
| FACP: Notifier NFS-320C FACP Location: Lobby System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2011 Most Recent Known Modification: N/A Year Opened: 1977 |
William D. Cuts Junior High School is a junior high school located at 149 Larose Drive, in St. Albert, Alberta, Canada. The school is part of the St. Albert Public School District. The school was built in 1977, and the fire alarm system was upgraded in 2011.
System Specifications (2011-present)
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the lobby. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Booster Panels
There are Notifier PSE-6C 6-amp booster power supplies controlling the horn/strobes in some portables.
Notification Appliances
Most notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
The new portable has System Sensor "L-Series" P2RLED-B horn/strobes (red, wall-mount, bilingual lettering, set to 15cd).
Initiating Devices
Pull Stations
Most pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Some areas have Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors in most areas.
There are Notifier FST-851HA addressable 190°F fixed-temperature heat detectors in one room.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There is a System Sensor "Innovair Flex" DNRA duct smoke detector housing with a Notifier FSP-851A addressable photoelectric head on the air handling unit.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
EOLs
There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.
Former System Specifications
| Former System Specifications |
|---|
| FACP: Simplex 4002 FACP Location: Foyer System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous Most Recent Known Modification N/A Year Installed: 1990 Year + Reason Decommissioned: 2011, lifecycle replacement |
FACP
The building was protected by a Simplex 4002 conventional fire alarm system. The panel was located in the foyer. The system coding was continuous.
Notification Appliances
Most notification appliances were Simplex 2901-9720 motor bells (6" gong).
The gymnasium had Simplex 2901-9722 motor bells (10" gong).
Initiating Devices
Pull Stations
All pull stations were Simplex 2099-9901 conventional single-action pull stations.
Automatic Detection Devices
There were Simplex 2098-9110 conventional ionization smoke detectors throughout the building.
One room had a Simplex 4255-54 conventional 194°F fixed-temperature heat detector.
The air handling unit had a Simplex 2098-9465 duct smoke detector housing with a Simplex 2098-9110 conventional ionization head.
EOLs
There were Simplex 2081-9018C end-of-line resistor plates on all circuits.