Kids & Company (Midnapore)

From FireAlarmPedia
Revision as of 16:28, 3 May 2026 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Mircom FX-2000<br />FACP Location: Main Entrance<br />System Type: Two-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR<br />System Coding: 20BPM (Alert)<br>Temporal (Alarm)<br>Strobes Synchronized: Yes, Mircom<br />Date of last known Upgrade: N/A<br />Most Recent Known Modification: N/A<br />Year Opened: 2011 |} '''Kids & Company''' is a chain of childca...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Mircom FX-2000
FACP Location: Main Entrance
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, Mircom
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2011

Kids & Company is a chain of childcare facilities. This particular facility is located at 15425 Bannister Road SE, in Calgary, Alberta, Canada. The building was built in 2011, and the fire alarm system is original.

System Specifications

Please note that these details are accurate to 2023.

FACP

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located at the main entrance. The system runs Mircom's CLIP addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, and the alarm signal coding is temporal.

Notification Appliances

Most notification appliances are Mircom "Select-A-Horn/Strobe" FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).
All classrooms have a mix of Mircom "Select-A-Strobe" FS-240W and FS-340W remote strobes (white, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Mircom MS-402AD addressable two-stage single-action pull stations.

Automatic Detection Devices

There are Mircom MIX-2251APA addressable photoelectric smoke detectors throughout most areas.
There are Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detectors in all storage, laundry and staff rooms, and in the kitchen.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There are System Sensor "Innovair Flex" DNRA duct smoke detector housings equipped with Mircom MIX-2251APA addressable photoelectric heads on all rooftop units.

Modules

There are Mircom MIX-M500MAPA addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Mircom MIX-M500RAPA addressable relay modules for RTU shutdown.
There are System Sensor M500XA isolator modules on the SLC.

EOLs

There are Mircom MP-300 end of line resistor plates on all sprinkler and signal circuits.