Acclaim Hotel by Clique Calgary Airport

From FireAlarmPedia
Revision as of 17:44, 3 September 2026 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: EST QuickStart QS4<br />FACP Location: Main Entrance Vestibule<br />System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR (FACP)<br>24VDC (Boosters)<br />System Coding: Temporal<br>Strobes Synchronized: Yes, Self-Sync<br />Date of last known Upgrade: N/A<br />Most Recent Known Modification: N/A<br />Year Opened: 2009 |} '''Acclaim Hotel by...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: EST QuickStart QS4
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR (FACP)
24VDC (Boosters)
System Coding: Temporal
Strobes Synchronized: Yes, Self-Sync
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2009

Acclaim Hotel by Clique Calgary Airport is a mid-range hotel located at 123 Freeport Blvd NE, in Calgary, Alberta, Canada. The building was built in 2009, and the fire alarm system is original excluding deficiency replacements.

System Specifications

FACP

The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature addressable protocol, and the system coding is temporal.

Annunciators

There is an EST RLCD annunciator behind the front desk.

Booster Panels

There are Edwards BPS6AC 6-amp booster power supplies in each electrical room.

Notification Appliances

All common area notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
All guest rooms have Edwards 683-1C silenceable mini-horns (white) paired with Edwards G1-VM remote strobes (white, wall-mount, no marking, set to 15cd).
For outdoor notification, there is an Edwards CS405-7A-T weatherproof remote strobe (red) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout all corridors, at the top of each stairwell, and in each elevator shaft.
There are EST SIGA2-PS and Edwards SIGA-PD/OSD addressable photoelectric smoke detectors as deficiency replacements.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in all mechanical and laundry rooms on floors 1-4.
All aforementioned detectors are mounted on EST SIGA-SB bases.
There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on all air handling units.
There are System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors in the basement laundry and mechanical rooms.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the heat detector zones, the kitchen suppression systems, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on both SLCs.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and on all Class B signal circuits.