| System Specifications |
|---|
| FACP: Mircom FA-1000 FACP Location: Building 4-1 North Entrance System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal? Strobes Synchronized: N/A Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 1981 |
Meadowbrook Apartments is an apartment complex located at 13531 Deer Run Blvd SE, in Calgary, Alberta, Canada. This page will cover Building 4, which was built in 1981. The fire alarm system is partially original.
System Specifications
Please note that this information is accurate to 2022.
FACP
The building is protected by a Mircom FA-1000 conventional fire alarm system. The panel is located at the Building 4-1 north entrance. The system coding is likely temporal.
Notification Appliances
All notification appliances are Edwards "Durabel" 6100D vibrating bells (6" gong).
Initiating Devices
Pull Stations
Most pull stations are Edwards 270-SPO conventional single-action pull stations.
Some areas have Summit SPS-101CA conventional single-action pull stations as deficiency replacements.
Automatic Detection Devices
There are System Sensor C2W-BA conventional photoelectric smoke detectors throughout all corridors and at the top of each stairwell.
There are FDD CR-135 conventional 135°F fixed-temperature/rate-of-rise heat detectors in all electrical and laundry rooms.
There are FDD CF-200 conventional 200°F fixed-temperature heat detectors in all furnace rooms.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all circuits.