Revision as of 17:52, 3 September 2026 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Simplex 4100ES<br />FACP Location: Main Lobby<br />System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC<br />System Coding: Temporal<br>Strobes Synchronized: Yes, SmartSync<br />Date of last known Upgrade: 2010s<br />Most Recent Known Modification: N/A<br />Year Opened: 1981 |} '''Sunrise Apartments''' is an apartment building located at 11...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Simplex 4100ES
FACP Location: Main Lobby
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: 2010s
Most Recent Known Modification: N/A
Year Opened: 1981

Sunrise Apartments is an apartment building located at 116 3 Ave SE, in Calgary, Alberta, Canada. The building was built in 1981, and the fire alarm system was upgraded in the 2010s.

System Specifications (2010s-present)

=FACP

The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main lobby. The system runs Simplex's IDNet addressable protocol, and the system coding is temporal.

Notification Appliances

All notification appliances are Simplex "TrueAlert" 4906-9127 horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices

There are Simplex "TrueAlarm" 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors in all apartments, in all garbage and mechanical rooms, and in all public washrooms.
There are Simplex 4098-9714 addressable photoelectric smoke detectors in all corridors, in all elevator lobbies, at the top of each stairwell, and at the top of the elevator shaft.
All aforementioned detectors are mounted on Simplex 4098-9792 bases.
There are Simplex 4098-9755 addressable photoelectric duct smoke detectors on all air handling units.
There is an FDD CF-200 conventional 200°F fixed-temperature heat detector in the generator room.

Modules

There are Simplex 4090-9001 addressable monitor modules supervising the generator room heat detector, and the sprinkler system's tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on the SLC.

EOLs

There are Electro Vox end of line resistor plates on all sprinkler and signal circuits.