Revision as of 17:53, 3 September 2026 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications (Atrium) |- | |- | FACP: Simplex 4100U<br />FACP Location: Main Entrance Vestibule<br />System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC<br />System Coding: Temporal<br>Strobes Synchronized: Yes, SmartSync<br />Date of last known Upgrade: Late 2000s<br />Most Recent Known Modification: N/A<br />Year Opened: 1982 |} '''Delta Hotels''' is a chain of mid-...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications (Atrium)
FACP: Simplex 4100U
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: Late 2000s
Most Recent Known Modification: N/A
Year Opened: 1982

Delta Hotels is a chain of mid-range hotels owned by Marriott. This particular hotel is located at 135 Southland Drive SE, in Calgary, Alberta, Canada. The hotel consists of two buildings: the atrium, built in 1982, and the tower, built in 1978. The fire alarm system in the atrium building was upgraded in the late 2000s, and the fire alarm system in the tower was upgraded in the late 2010s.
The fire alarm systems in both buildings are interconnected via relay and monitor modules, however the sequence of operations is not known.

System Specifications (Atrium, 2000s-present)

FACP

The building is protected by a Simplex 4100U addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex's IDNet addressable protocol, and the system coding is temporal.

Notification Appliances

All notification appliances are Simplex "TrueAlert" 4906-9129 horn/strobes (white, wall-mount, set to 15cd).
Simplex 4098-9794 sounder bases are used in guest rooms in lieu of standard notification appliances.

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices

There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors in all corridors and guest rooms, at the top of each stairwell, and throughout the atrium.
There are Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
All aforementioned detectors installed in common areas are mounted on Simplex 4098-9792 bases; all aforementioned detectors installed in guest rooms are mounted on Simplex 4098-9794 sounder bases.
There are Simplex 4098-9755 addressable photoelectric duct smoke detectors on all air handling units.

Modules

There are SImplex 4090-9001 addressable monitor modules supervising the kitchen suppression system, and the sprinkler system's tamper and flow switches; two additional modules are used for receiving alarm and trouble signals from the tower building.
There are Simplex 4090-9002 addressable relay modules serving various purposes, including sending alarm and trouble signals to the tower building.
There are Simplex 4090-9116 addressable isolator modules on the SLCs.

EOLs

There are Simplex 2081-9040C end of line resistor plates on all kitchen suppression, sprinkler and signal circuits.


System Specifications (Tower, 2010s-present)

System Specifications (Tower)
FACP: Mircom FX-2000
FACP Location: Behind Front Desk
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: Late 2010s
Most Recent Known Modification: N/A
Year Opened: 1978

FACP

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located behind the front desk. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.

Notification Appliances

All common area notification appliances are Mircom "Select-A-Horn/Strobe" FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).
All guest rooms have System Sensor "SpectrAlert Advance" MHWZA silenceable mini-horns (white).

Initiating Devices

Pull Stations

All pull stations are Mircom MS-401AP addressable single-action pull stations.

Automatic Detection Devices

There are Mircom MIX-2251APA addressable photoelectric smoke detectors in all corridors, in all elevator lobbies, in the skywalk to the atrium building, and at the top and every third landing of each stairwell.
There are Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
Most aforementioned detectors are mounted on System Sensor B210LPA bases; detectors at fire separations are mounted on System Sensor B224BIA isolator bases.
There are System Sensor "Innovair Flex" DNRA duct smoke detector housings equipped with Mircom MIX-2251APA addressable photoelectric heads on all air handling and makeup air units.

Modules

There are Mircom MIX-M500MAPA addressable monitor modules supervising the generator's run/trouble contacts, the kitchen suppression system, and the sprinkler system's tamper and flow switches; two additional modules are used for receiving alarm and trouble signals from the atrium building.
There are Mircom MIX-M500RAPA addressable relay modules serving various purposes, including elevator recall and sending alarm/trouble signals to the atrium building.
There are System Sensor M500XA isolator modules on the SLC.

EOLs

There are Mircom MP-300 end of line resistor plates on all circuits supervised by monitor modules (excluding link circuits), and on all signal circuits.

Former System Specifications (Tower, 1978-2010s)

Former System Specifications (Tower)
FACP: Mircom Series FA-1000
FACP Location: Behind Front Desk
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal?
Strobes Synchronized: N/A
Most Recent Known Modification: N/A
Year Installed: 1978
Year + Reason Decommissioned: 2010s, System Upgrade

Please note that this information is unconfirmed.

FACP

The building was protected by a Mircom Series FA-1000 conventional fire alarm system. The panel was located behind the front desk. The system coding was likely temporal.
The original FACP was likely a Simplex 2001.

Notification Appliances

All notification appliances were Mircom BL-6B motor bells (6" gong).

Initiating Devices

Pull Stations

All pull stations were Simplex 4251-20 conventional single-action pull stations.

Automatic Detection Devices

There were System Sensor C2W-BA conventional photoelectric smoke detectors in all corridors and at the top of each stairwell.
There were FDD CR-135 conventional 135°F fixed-temperature/rate-of-rise heat detectors in some areas.

EOLs

There were Simplex 2081-9018C end of line resistor plates on all circuits.