More actions
System Specifications |
---|
FACP: Notifier AFP-200C System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC Date of last known Upgrade: N/A Year Opened: 2005 |
Days Inn is a hotel chain owned by Wyndham. They have hotels across North America. This particular hotel is located in Red Deer, Alberta. It was built in 2005, and has the original fire alarm system.
Note: Some details of the system are unknown, as the system has only been spotted via Google Maps.
System Specifications
FACP
The hotel is protected by a Notifier AFP-200C addressable fire alarm system. The panel is located at the main entrance. The system runs Notifier’s CLIP addressable protocol, and does code 3 in alarm.
Notification Appliances
All notification appliances are System Sensor “SpectrAlert” P1224MCWA horn/strobes (white, wall-mount). These are found everywhere in the hotel, including the guest rooms. The strobes are not synchronized.
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX CLIP addressable dual-action pull stations.
Automatic Detection Devices
None noticed, but should be present.
Bonus Information
This hotel has the oldest known Notifier NBG-12LX pull stations in Alberta!
According to a TripAdvisor review, in August 2015 the fire alarm was activated a smoke detector on the system at 1:30 AM. There were reports of smoke and a burning smell, meaning there was a real emergency. The system did its job, and it still works.