Crowfoot Library

From FireAlarmPedia
Revision as of 13:58, 3 April 2023 by Twentytwo22 (talk | contribs)
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: 2014
Year Opened: 2004

The Crowfoot Library is a public library located at 8665 Nose Hill Drive Northwest, in Calgary, Alberta, Canada. It is part of the Calgary Public Library. The building opened in 2004, and the fire alarm system is mostly from 2014. All of the notification appliances are original.

System Specifications (2014-present)

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule, between two book return slots. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All notification appliances are System Sensor "SpectrAlert" P2415A horn/strobes (red, wall-mount, 15cd). These are mounted on the ceiling throughout the library.

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the library, mounted on System Sensor B210LPA low-profile bases.

Former System Specifications (2004-2014)

Former System Specifications
FACP: Simplex 4010
FACP Location: Main Entrance
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: N/A
Year Decommissioned: 2014

FACP

The building was protected by a Simplex 4010 addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran Simplex's IDNet addressable protocol, and the system coding was temporal.

Notification Appliances

All notification appliances were System Sensor "SpectrAlert" P2415A horn/strobes (red, wall-mount, 15cd). These are still in use on the Notifier system, and were likely installed due to customer preference.

Initiating Devices

Pull Stations

All pull stations were Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices

There were Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors throughout the library, mounted on Simplex 4098-9792 addressable bases. [[]