System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Main Entrance System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, SS Date of last known Upgrade: 2016 Year Opened: 1960s |
Alberta Health Services is the governing body of health care services in the province of Alberta. This page will cover EMS Station #4, located at 16 Moncton Road Northeast, in Calgary, Alberta, Canada. The station opened in 1971 as a fire station, and was converted to an EMS station in the 1990s. The fire alarm system was fully upgraded in 2016.
System Specifications (2016-present)
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances
All notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, and a Notifier FST-851A addressable 135°F fixed-temperature heat detector in the kitchen. All detectors are mounted on System Sensor B210LPA bases.