System Specifications
FACP: EST QuickStart QS4
FACP Location: Basement Telecom Room
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: 20BPM (alert)
Temporal (alarm)
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2004

Newport Harbour Care Centre is a long-term care facility or nursing home located at 10 Country Village Cove NE, Calgary, AB. It was built in 2004, and has the original fire alarm system.

System Specifications (2004-present)

FACP

The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel is located in the basement telecom room. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. The alert signal is 20BPM, followed by the temporal alarm signal.

Booster Panels

There are three Edwards BPS10A 10 amp booster power supplies next to the panel.

Notification Appliances

All notification appliances are EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building.
There are EST SIGA-HRS addressable fixed/rate-of-rise heat detectors in the crawlspaces and staff rooms.
All EST detectors are mounted on SIGA-SB bases.
The kitchens have FDD CF-135 135 degree fixed-temperature heat detectors, wired to EST SIGA-CT1 addressable monitor modules.
There are EST SIGA-DH duct detector housings with SIGA-PS addressable photoelectric smoke detector heads on all air handling units.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.