System Specifications |
---|
FACP: Mircom FX-2000
FACP Location: Main Electrical Room System Type: Hybrid System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Steady Strobes Synchronized: N/A Date of last known Upgrade: 2021 Year Opened: 1980 |
EQ Bank Tower is a multi-story tower located at 906 12 Ave SW, Downtown Calgary. It was built 1979-1980 according to building officials and verified with historical aerial imagery. The system is 60% original overall.
System Specifications
FACP
The building is protected by a Mircom FX-2000 hybrid addressable fire alarm system. The panel is located in the main electrical room, and is in a BBX-1072A cabinet. Despite being an addressable panel, the system is mostly conventional but the main and fourth floors have been converted to addressable. It was likely installed in the early 2000s. From the devices installed throughout, it is most definitely an original Edwards 6500 as evident by the abandoned annunciator behind the current annunciator. The addressable parts of this system run Mircom's CLIP addressable protocol, and the system coding is continuous.
Annunciators
There is one RAX-LCD in the front lobby. Mounted to the front door of the old Edwards 456 annunciator cabinet.
Notification Appliances
Most notification appliances are Mircom BL-10A and BL-10B motor bells (10" gong).
There are a few Mircom BL-6A/BL-6B motor bells (6" gong) mixed in.
Initiating Devices
Pull Stations
Conventional
About 80% of the conventional pull stations are original Edwards 270-SPO (single action, break glass) with the original solid glass rod.
There are a few Mircom MS-401 single-action pull stations as deficiency replacements.
Addressable
There are Mircom MS-401AD (single-action) addressable pull stations installed throughout the 1st and 4th floors.
Automatic Detection Devices
Conventional
There is an equal variety of Edwards 281C fixed/rate-of-rise and FDD CR-135 fixed/rate of rise heat detectors installed. Along with several Mirtone (model?) bi-metal type self-restoring heat detectors.
Addressable
There are of Mircom MIX-2251AP (photo) detectors installed on the 4rd floor.
One Mircom MIX-5351RAPA (rate of rise) heat detector recently installed at one of the tenant entrances. Along with a Mircom MIX-5251RAPA (rate of rise) heat detector in the loading dock, the main telephone room and one in the main electrical room. Finally, there is a MIX-5251HAPA (200°F) addressable heat detector in the generator room. [[]