Cape Cod Hospital

From FireAlarmPedia
Revision as of 12:51, 16 March 2024 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Edwards EST3 <br />FACP Location: Main Electrical Room <br />System Type: Addressable...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST3
FACP Location: Main Electrical Room
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: 20BPM Chime
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 2008
Year Opened: 1920

Cape Cod Hospital is a hospital located at 27 Park Street, in Hyannis, Massachusetts, USA. The hospital was built in 1920, and the fire alarm system was upgraded in 2008.

System Specifications (2008-present)

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the main electrical room. The system runs Edwards’ Signature addressable protocol, and is equipped with voice evacuation. The alarm signal is a 20BPM chime tone, and the horn/strobe coding is temporal.

Annunciators

There is an Edwards EST3-LCDANN annunciator at the emergency room ambulance entrance.

Notification Appliances

Most common areas have Edwards “Genesis” G4RF-S7VM speaker/strobes (red, wall-mount, FIRE marking, set to 15cd).
Some areas have Edwards GCF-S7VM speaker/strobes (white, ceiling-mount, FIRE marking, 70V, set to 15cd).
Some rooms and smaller areas have Edwards G1RF-VM remote strobes (red, wall-mount, FIRE marking, 70V, set to 15cd) or Edwards GCF-VM remote strobes (white, ceiling-mount, FIRE marking, set to 15cd).
For outdoor notification, there is an Edwards “Integrity” 757-7A-T horn/strobe (red, wall-mount, 15/75cd) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-278 addressable dual-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building.
The emergency room has EST SIGA2-PS addressable photoelectric smoke detectors.
All detectors are mounted on EST SIGA-SB bases.
There are EST “SuperDuct” SIGA-SD addressable photoelectric duct smoke detectors on all air handling units, equipped with EST SIGA-DTS test switches.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the boilers and the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules controlling HVAC systems throughout the building.