System Specifications
FACP: Edwards EST3X
FACP Location: Main Entrance Vestibule
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2022


The Circle at Seton is a group of apartment buildings located on Seton Circle SE, Calgary. This page will cover building 1134, located at 1134 Seton Circle SE, Calgary, AB. It was built in 2022, and the fire alarm system is original.

System Specifications (2022-present)

FACP

The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Edwards’ Signature addressable protocol, and the system coding is temporal.

Notification Appliances

Most notification appliances are from Edwards’ “Genesis LED” line of products.
Most notification appliances are Edwards G1AVWN horn/strobes (white, wall-mount, no marking, set to 15cd). These are on all above-ground floors.
The parkade has a mix of Edwards G1AVRN horn/strobes (red, wall-mount, no marking, set to 15cd) and G1VRF remote strobes (red, wall-mount, no marking, set to 15cd).
Each suite has an Edwards G1VWF remote strobe (white, wall-mount, no marking, set to 15cd) in the living room, and an Edwards 683-1C mini-horn (white, silenceable) in each bedroom.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are Edwards SIGA-OSD addressable optical smoke detectors throughout the corridors, mounted on SIGA-SB bases.
There is an EST SIGA-SD addressable photoelectric duct smoke detector on the make-up air unit.

Modules

There are EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Edwards SIGA-CR addressable relay modules for HVAC shutdown and elevator recall.
Each SLC has an Edwards SIGA-IM isolator module.